Commercial HVAC Freeze Prep for Texas Buildings

Furnace maintenance in dfw

Dallas-Fort Worth does not get many hard freezes, which is exactly why they cause so much damage. Buildings are designed for heat, not ice. When temperatures drop into the teens or below for a day or more, frozen pipes, cracked coils, iced-up heat pumps and failed heating sections all show up at once, and every contractor in the area is booked. A short freeze plan made in the fall can save a lot of damage and downtime.

Before winter: the fall checklist

  • Heating start-up on every unit. Test gas heat sections (ignition, flame sensing, heat exchanger) and heat pump defrost controls and backup heat. A unit that has not run heat since last winter is the one most likely to fail on the coldest night.
  • Economizers and outside-air dampers. Confirm they close properly. A damper stuck open can pull freezing air across water coils and into the building.
  • Low-ambient and freeze-stat settings. Check that freeze protection controls on water-source and hydronic equipment are set and working.
  • Insulation and heat trace. Inspect insulation on exposed piping, condensate lines and water lines on the roof or in unheated spaces. Test any heat trace.
  • Building automation and thermostats. Set minimum temperatures for unoccupied periods so heat never shuts off completely.

When a hard freeze is forecast

  1. Keep heat on everywhere, including vacant suites, stairwells and mechanical rooms. Set a minimum around the mid-50s in unoccupied spaces.
  2. Open interior doors to closets and rooms with plumbing on exterior walls so heat reaches them.
  3. Check rooftop condensate and water lines for insulation gaps.
  4. Water-source heat pump and cooling tower systems: confirm loop temperature controls, boiler or heat-addition equipment and freeze protection. Talk to your service provider before the freeze about running circulation pumps continuously.
  5. Restaurants: make sure walk-in cooler and freezer condensing units and their drains are protected and running normally.
  6. Know your shutoffs. Make sure staff know where the main water and gas shutoffs are.
  7. Line up emergency contacts for HVAC, plumbing and the building engineer, and share them with tenants.

Heat pumps in a freeze

Heat pumps lose capacity as outdoor temperatures drop and lean on backup electric heat. Expect more frequent defrost cycles and higher electricity use. Make sure backup heat works before the cold arrives, and keep snow and ice from piling around outdoor units. A heat pump outdoor unit encased in ice that does not clear needs service.

After the freeze

  • Walk the roof and mechanical spaces for leaks, cracked coils, and split pipes once temperatures rise. Damage often shows up as water only after thawing.
  • Check that every unit is heating, then cooling normally when the weather turns.
  • Document any damage with photos for insurance and planning.

Plan it once, repeat every year

The easiest way to stay ready is to build freeze prep into your fall service visit. A commercial maintenance agreement covers heating start-up on every unit, and priority status matters when everyone is calling at once. If something does fail during a freeze, our 24/7 emergency service is available. See also our rooftop unit maintenance schedule.

Frequently asked questions

How do I protect commercial HVAC from freezing?

Do a full heating start-up in the fall, confirm dampers close, check freeze protection controls and pipe insulation, keep heat on in all spaces including vacant suites, and line up emergency contacts before a freeze.

What temperature should vacant commercial spaces be kept at in a freeze?

Keep heat on with a minimum around the mid-50s so pipes and equipment in walls and ceilings stay above freezing.

Can rooftop units freeze?

Water coils, condensate lines and piping on or near rooftop units can freeze, and outside air dampers that stick open can let freezing air into the building.

What should I check after a hard freeze?

Walk roofs and mechanical spaces for leaks, cracked coils and split pipes after thawing, and confirm every unit heats properly.

Need help with your commercial HVAC?

CandelTech Services works with property managers and business owners across Dallas-Fort Worth: repairs, maintenance agreements and replacements, with 24/7 emergency service.

Call 817-616-3405  ·  Text 817-646-7517  ·  Request a quote